NKG-3经纬度时控开关英文说明书
NKG-3 Time Switch
(The time switch can be automatically adjusted according to the latitude and longitude of the switching time.)
1. Function and Scope
NKG-3 time switch (hereinafter referred to as ‘time switch’) is applicable for controlling switch-on and off of street lamps, advertising light boxes and other equipments in automatic control circuit with AC frequency of 50Hz, rated control power voltage of 220V at most and rated working current of 3A at most. The product may be used to adjust the switch-on and off time everyday according to the latitude.
The product complies with the requirements of Standard GB 14048.5 and IEC 60947-5-1.
2. Model and Its Meaning
3. Normal Operating Condition and Installation Condition
3.1 Ambient air humidity: -5℃~+40℃, and the average temperature is no more than +35℃ in 24h.
3.2 Altitude: no more than 2,000m.
3.3 Humidity: the relative air humidity of the installation site shall be no more than 50% when the maximum temperature is +40℃, while it can be higher under lower temperature. Special measures shall be taken for the condensation occasionally formed due to temperature change.
3.4 Pollution level: 3.
3.5 In the medium with explosion hazard and no gas that is enough to corrode metal and destroy the insulation and the place shall not have severe conductive dust.
3.6 In the place where is provided with anti-snow and anti-rain equipment but not be full of water steam.
3.7 In the place without significant shake, shock and vibration.
3.8 Installation class: II.
3.9 Transport and Storage Conditions: -25℃ to +55℃.
3.10 Power voltage change scope: 85%~110% rated operating voltage.
3.11 Protection grade: IP20.
4 Main Technical Parameters
4.1 Rated control power voltage: 50Hz AC220V.
4.2 Conventional thermal current: Ith 16A.
4.3 Category of the control circuit: AC-15.
4.4 Rated working current (Ie): AC-15 220V 3A.
4.5 Timing error: ≤1s/d.
4.6 Time control scope: 1min~168h.
4.7 Dimension setting range: N/S -60 ° ~+60 °.
4. Mechanical